The GesySense Digital-Logger offers 2 functionalities:
The Digital-Logger operates analog to the Sersor version but stores measured pulses or status modifications in its local memory. Along with this operation mode measured values can be radio transmitted as well immediately. The logger stores 15-minute value in a memory which is even preserved at a battery failure. Correct operation of the module is indicated by a LED.
As Status-Logger it is used to monitor devices and system components. It reads the status of connected passive contacts.
The Status-Logger records the status of the connected contacts at a fixed interval. To avoid that „oscillating“ contacts generate false alarms, there must be a minimum period of time for a status message to be considered as valid.
As Counter-Logger the module records pulses up to 20 Hz at its 2 digital inputs and stores the values locally. The resolution is 32 bit. The meter reading of the previous interval is reported in the defined transmission interval.
Operation of the two inputs can only be set for both as status or counter inputs using the GesySense configuration software.
other components